hawke cable gland 501/421

Compression Gland

Hawke Cable Gland 501/421

The 501/421 dual certified Exe/Exd cable gland is intended for use on non-armoured elastomer and plastic insulated cables. This cable gland may be used with braided cables where the braid and outer sheath pass into the enclosure. The braid must then be suitably terminated inside the enclosure. For Exd applications, the cable must be suitable in compliance with BS EN 60079-14.

Technical Data

Cable Gland 501/421

  • Ingress Protection: IP66, IP67 and IP68 (30 metres for 7 days, special conditions may apply) to IEC/EN 60529 and NEMA 4X
  • Deluge Protection: Deluge Protection to DTS01
  • Operating Temperature: -60°C to +100°C
  • ATEX/IECEx Protection Class: Ex II 2GD Ex db IIC Gb; Ex eb IIC Gb; Extb IIIC Db
  • ATEX Certificate No: CML 19ATEX1167X
  • IECEx Certificate No: CML 19.0045X
  • Construction & Test Standards: IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 60079-31
  • Additional Certifications:
    EAC: RU C-GB.AA87.B.00430
    Inmetro: IEx 14.0272X
    KCs: KTL 17-KA4BO-0120X to 0128X
    India: PESO P450038
    China: CNEx17 2858X
  • NEC Protection Class Class: I, Zone I, AEx eb IIC Gb; Zone 21, AEx tb IIIC Db
  • CEC Protection Class: Class: I, Div.2 Groups ABCD; Class II Div.2, Groups EFG; Class III; Ex db IIC Gb; Ex eb IIC Gb
  • c CSA us Certificate Number: CSA1015065
  • Construction & Test Standards: UL 60079-0, UL 60079-7, UL 60079-31, CSA 22.2 No: 60079-0,
    CSA 22.2 No: 60079-1, CSA 22.2 No: 60079-7, CSA 22.2 No: 60079-31, UL514B; UL1203; UL 2225