Cable Glands

North American Cable Glands/Connectors

Explosion Proof
IECEx and ATEX Approved Flameproof Exd,
Increased Safety Exe and Restricted Breathing ExnR
(Note: Dual Marked UL & ATEX as standard).

Application
• Outdoor or indoor use.
• For use with continuous corrugated aluminium Metal Clad (MCHL) cable.
• See technical section for installation rules and regulations. 

Technical Data

• UL Listing No: E84940.
• Suitable for use in:
• Class 1, Division 1, Gas Groups A, B, C and D
• Class 1, Zone 2, Gas Groups IIA, IIB and IIC
• AExd IIC and AExe II Class 1, Zone 2.
• Flameproof Exd, Increased Safety Exe II 2 GD and Restricted
Breathing ExnR II 3G.
• Certificate No’s: Sira 06ATEX1295X and IECEx SIR 06.0082X.
• Suitable for use in Zone 1, Zone 2, Zone 21, Zone 22 and in Gas
Groups IIA, IIB and IIC.
• Construction and Test Standards: UL 2225, IEC/EN 60079-0,
IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-15 and IEC/EN 60079-31
• Ingress Protection: IP66, IP67 and IP 68 (30 metres for 7 days) to
IEC/EN 60529 and NEMA 4X.
• Deluge Protection to DTS01.
• Operating Temperature Range: -50°C to +60°C (UL) and -60°C to
+80°C (ATEX / IECEx).
• Assembly Instruction Sheet: AI 317 (UL) and AI 338 (ATEX / IECEx).
• Alternative certification options available:

Ordering Information
Format for ordering is as follows:

Cable Gland / Connector Type

711

Size

c

Thread

1″ NPT

Features

• Provides 360° armour grounding which is fully Inspectable.
• Grounding Device remains in contact with cable when
disassembled for inspection.
• Provides a barrier seal between the individual insulated
conductors within the cable and prevents entry of the
products of an explosion into the cable.
• Assembly of the cable gland compresses and distributes the
compound evenly to effect a barrier seal at the point of entry
into the enclosure.
• Provides an outer deluge seal to prevent moisture ingress
to the cable armour and enclosure. Deluge seal is coloured red
to indicate Hazardous Location product.
• Provides a cable retention and low smoke and fume, zero
halogen seal onto the cables outer jacket.
• Manufactured in Brass (standard), Nickel Plated Brass,
316 Stainless Steel or Aluminium.
• Brass NPT entries are nickel plated as standard. 

Two part sealing compound and assembly instructions are supplied with the cable gland.